The Testo 310 Flue Gas Analyser combines simple functions with a high level of measurement accuracy and is perfect for all basic measurements on heating systems. Long battery lifetimes of up to 10 hours guarantee high availability. Its easy handling and compact design make the testo 310 a robust tool for daily work – even when things get rough.
With its capability to perform both basic or more complex combustion analysis, perform maintenance or safety checks, or confirm boiler efficiency, the fully-featured testo 310 residential combustion analyser is ready to provide accurate analysis. The stainless steel probe and cone-stop are perfect for residential and boiler efficiency applications. Simple top-of-display icons show you the current measurement functions. After only 30 seconds, the 310 is ready to test. With five different fuels to select from (Natural Gas, Propane, Fuel Oil 2, Biomass 5%, Wood 20%), it provides the flexibility you need for all your residential combustion analysis applications.
Measures:
O2, CO (with built-in NOx filter), CO2
Undiluted CO (CO air free)
Ambient CO
Draft & Pressure
Temperature (flue & ambient)
Combustion/flue gas efficiency & excess air
Delivery Scope
testo 310 - Flue Gas Analyser, Hard case, rechargeable battery, USB mains cable, silicon hose for pressure, 5 x filters, calibration protocol, 180mm probe with cone, spare pressure plugs.
Specification
Testo 310 Flue Gas Analyser Standard Kit Specification
Temperature - TC Type K (NiCr-Ni)
Measuring range
-20 to +100 °C
Accuracy
±1 °C
Resolution
0.1 °C
Reaction time
< 50 s
Temperature (ambient temperature)
Temperature - TC Type J (Fe-CuNi)
Measuring range
0 to +400 °C
Accuracy
±1 °C (0 to +100 °C)±1.5 % of mv (> 100 °C)
Resolution
0.1 °C
Reaction time
< 50 s
Temperature (flue gas)
Flue gas O2
Measuring range
0 to 21 Vol.%
Accuracy
±0.2 Vol.%
Resolution
0.1 Vol.%
Reaction time t90
30 s
Flue gas Draught
Measuring range
-20 to +20 hPa
Accuracy
±0.03 hPa (-3.00 to +3.00 hPa)±1.5 % of mv (Remaining Range)
Resolution
0.01 hPa
Flue gas degree of effectivity, Eta (calculated)
Measuring range
0 to 120 %
Resolution
0.1 %
Flue gas loss (calculated)
Measuring range
0 to 99.9 %
Resolution
0.1 %
Flue gas CO₂ calculation (calculated from O₂)
Measuring range
0 to CO₂ max (Display range)
Accuracy
±0.2 Vol.%
Resolution
0.1 Vol.%
Reaction time t₉₀
< 40 s
Pressure measurement
Measuring range
-40 to +40 hPa
Accuracy
±0.5 hPa
Resolution
0.1 hPa
Flue gas CO (without H₂-compensation)
Measuring range
0 to 4000 ppm
Accuracy
±20 ppm (0 to 400 ppm)±5 % of mv (401 to 2000 ppm)±10 % of mv (2001 to 4000 ppm)
Resolution
1 ppm
Reaction time t90
60 s
Ambient CO
Measuring range
0 to 4000 ppm
Accuracy
±20 ppm (0 to 400 ppm)±5 % of mv (401 to 2000 ppm)±10 % of mv (2001 to 4000 ppm)
Resolution
1 ppm
Reaction time
60 s
General technical data
Dimensions
201 x 83 x 44 mm
Operating temperature
-5 to +45 °C
Display type
LCD
Display function
Backlit 2-line display
Power supply
Battery: 1500 mAh, mains unit 5V/1A
Storage temperature
-20 to +50 °C
Weight
(with probe) Approx. 700 g
Features
Testo 310 Flue Gas Analyser Standard Kit Features
Simultaneous measurement of O2, CO, and flue gas and ambient temperatures
Measurement menus for flue gas, draught, CO environment and pressure
Sensor zeroing in 30 seconds
Rechargeable lithium battery for up to 10 hours of operation
Reading printout with a portable printer
Robust construction
Being a systems mechanic, you know only too well how tough things can get when you're working out in the field. That's why your measuring tools need to be rugged and reliable, like the testo 310 flue gas analyser. Designed especially for use in the field.